Wire Size Chart — NEC Ampacity Table

This page provides a complete reference table of all standard wire gauges from 14 AWG to 500 kcmil, with ampacity ratings from NEC Table 310.16 for both copper and aluminum conductors at all three standard temperature ratings. Use this chart to quickly determine the maximum allowable current for any wire size, or click on a specific gauge to see detailed voltage drop tables, common applications, and installation guidance.

Copper Conductor Ampacity (NEC Table 310.16)

Copper is the most widely used conductor material in residential and commercial electrical installations. The table below shows the maximum continuous ampacity for copper conductors installed in raceways, cables, or directly buried, based on an ambient temperature of 30 degrees C (86 degrees F) with not more than three current-carrying conductors in the raceway or cable. These values come directly from NEC Table 310.16 and represent the maximum current each gauge can safely carry without exceeding its temperature rating.

Wire Gauge Diameter (in) Area (CM) Resistance (Ω/kft) 60°C 75°C 90°C
14 AWG 0.0641 4,110 3.14 15 A 20 A 25 A
12 AWG 0.0808 6,530 1.98 20 A 25 A 30 A
10 AWG 0.1019 10,380 1.24 30 A 35 A 40 A
8 AWG 0.1285 16,510 0.778 40 A 50 A 55 A
6 AWG 0.162 26,240 0.491 55 A 65 A 75 A
4 AWG 0.2043 41,740 0.308 70 A 85 A 95 A
3 AWG 0.2294 52,620 0.245 85 A 100 A 115 A
2 AWG 0.2576 66,360 0.194 95 A 115 A 130 A
1 AWG 0.2893 83,690 0.154 110 A 130 A 145 A
1/0 AWG 0.3249 105,600 0.122 125 A 150 A 170 A
2/0 AWG 0.3648 133,100 0.0967 145 A 175 A 195 A
3/0 AWG 0.4096 167,800 0.0766 165 A 200 A 225 A
4/0 AWG 0.46 211,600 0.0608 195 A 230 A 260 A
250 kcmil 0.5 250,000 0.0515 215 A 255 A 290 A
300 kcmil 0.548 300,000 0.0429 240 A 285 A 320 A
350 kcmil 0.592 350,000 0.0367 260 A 310 A 350 A
400 kcmil 0.632 400,000 0.0321 280 A 335 A 380 A
500 kcmil 0.707 500,000 0.0258 320 A 380 A 430 A

Aluminum Conductor Ampacity (NEC Table 310.16)

Aluminum conductors have lower ampacity than copper for the same gauge size due to aluminum's higher resistivity. However, aluminum is significantly lighter and less expensive, making it the preferred choice for large service entrance conductors, feeder circuits, and utility distribution. The table below shows aluminum ampacity values from NEC Table 310.16 at all three temperature ratings. When using aluminum, always verify that terminations are rated for aluminum conductors (AL-CU marking) and apply anti-oxidant compound to all connections.

Wire Gauge Resistance (Ω/kft) 60°C 75°C 90°C
14 AWG 5.17 12 A 16 A 20 A
12 AWG 3.25 16 A 20 A 24 A
10 AWG 2.04 24 A 28 A 32 A
8 AWG 1.28 32 A 40 A 44 A
6 AWG 0.808 44 A 52 A 60 A
4 AWG 0.508 56 A 68 A 76 A
3 AWG 0.403 68 A 80 A 92 A
2 AWG 0.319 76 A 92 A 104 A
1 AWG 0.253 88 A 104 A 116 A
1/0 AWG 0.201 100 A 120 A 136 A
2/0 AWG 0.159 116 A 140 A 156 A
3/0 AWG 0.126 132 A 160 A 180 A
4/0 AWG 0.1 156 A 184 A 208 A
250 kcmil 0.0847 172 A 204 A 232 A
300 kcmil 0.0707 192 A 228 A 256 A
350 kcmil 0.0605 208 A 248 A 280 A
400 kcmil 0.0529 224 A 268 A 304 A
500 kcmil 0.0424 256 A 304 A 344 A

Understanding the Ampacity Table

The ampacity values in NEC Table 310.16 represent the maximum continuous current a conductor can carry without exceeding its insulation temperature rating. These values assume standard conditions: an ambient temperature of 30 degrees C (86 degrees F) and no more than three current-carrying conductors in a raceway or cable. When conditions deviate from these assumptions, adjustment and correction factors must be applied.

The three temperature columns correspond to different insulation types. The 60 degrees C column applies to TW and UF insulation types and is the baseline for most older residential installations. The 75 degrees C column covers THW, THWN, and XHHW insulation types and is the most commonly referenced column for modern installations. The 90 degrees C column applies to THHN, THWN-2, and XHHW-2 types and is primarily used as a starting point for ampacity derating calculations rather than as the actual conductor ampacity.

When selecting a wire gauge, remember that the conductor itself is often rated for 90 degrees C, but the circuit must be sized based on the lowest temperature rating of any component. Most residential circuit breakers and devices have 75 degrees C rated terminals, so even with 90 degrees C wire, you must use the 75 degrees C ampacity column. The 90 degrees C rating becomes valuable when you need to apply ampacity adjustment factors for bundled conductors or high ambient temperatures, as the higher starting ampacity provides additional margin.

For circuits with more than three current-carrying conductors in a raceway, NEC Table 310.15(C)(1) requires reducing the ampacity. For 4-6 conductors, the adjustment factor is 80%. For 7-9 conductors, it is 70%. These reductions account for the increased heat generated when multiple conductors share the same confined space. Similarly, if the ambient temperature exceeds 30 degrees C, correction factors from NEC Table 310.15(B)(1) must be applied to reduce the ampacity accordingly.

Wire Gauge Quick Reference

Click any wire gauge below for a dedicated page with detailed voltage drop tables at various distances, common applications, NEC code references, and installation tips specific to that conductor size.