10 AWG Wire — Ampacity & Voltage Drop

Complete specifications for 10 AWG conductors including ampacity ratings from NEC Table 310.16, resistance values from NEC Chapter 9 Table 8, and pre-computed voltage drop tables at multiple distances. The 10 AWG conductor has a cross-sectional area of 10,380 circular mils and a diameter of 0.1019 inches. Use the tables below for quick reference, or use the wire size calculator for custom parameters.

10 AWG Specifications

Diameter
0.1019 in
Area
10,380 CM
Cu Resistance
1.24 Ω/kft
Al Resistance
2.04 Ω/kft

Ampacity Ratings (NEC Table 310.16)

Material 60°C 75°C 90°C
Copper 30 A 35 A 40 A
Aluminum 24 A 28 A 32 A

Voltage Drop Table — 10 AWG Copper at 120V

The table below shows the voltage drop in volts and percentage for 10 AWG copper conductors at 120 volts, single-phase, at various distances and amperages. Cells highlighted in red exceed the NEC recommended 3% voltage drop limit for branch circuits. Use these values to quickly determine if 10 AWG is adequate for your 120-volt circuit at the planned distance, or if you need to upsize to a larger gauge.

Distance 15A20A30A40A50A
25 ft 0.9V
0.8%
1.2V
1.0%
1.9V
1.6%
2.5V
2.1%
3.1V
2.6%
50 ft 1.9V
1.6%
2.5V
2.1%
3.7V
3.1%
5.0V
4.1%
6.2V
5.2%
75 ft 2.8V
2.3%
3.7V
3.1%
5.6V
4.7%
7.4V
6.2%
9.3V
7.8%
100 ft 3.7V
3.1%
5.0V
4.1%
7.4V
6.2%
9.9V
8.3%
12.4V
10.3%
125 ft 4.7V
3.9%
6.2V
5.2%
9.3V
7.8%
12.4V
10.3%
15.5V
12.9%
150 ft 5.6V
4.7%
7.4V
6.2%
11.2V
9.3%
14.9V
12.4%
18.6V
15.5%
200 ft 7.4V
6.2%
9.9V
8.3%
14.9V
12.4%
19.8V
16.5%
24.8V
20.7%
250 ft 9.3V
7.8%
12.4V
10.3%
18.6V
15.5%
24.8V
20.7%
31.0V
25.8%
300 ft 11.2V
9.3%
14.9V
12.4%
22.3V
18.6%
29.8V
24.8%
37.2V
31.0%
400 ft 14.9V
12.4%
19.8V
16.5%
29.8V
24.8%
39.7V
33.1%
49.6V
41.3%
500 ft 18.6V
15.5%
24.8V
20.7%
37.2V
31.0%
49.6V
41.3%
62.0V
51.7%

Voltage Drop Table — 10 AWG Copper at 240V

The following table shows voltage drop for 10 AWG copper conductors at 240 volts, single-phase. Because 240-volt circuits have a higher supply voltage, the percentage voltage drop is lower for the same absolute voltage loss. This means 10 AWG wire can run longer distances on a 240-volt circuit before exceeding the 3% limit compared to a 120-volt circuit carrying the same current.

Distance 15A20A30A40A50A
25 ft 0.9V
0.4%
1.2V
0.5%
1.9V
0.8%
2.5V
1.0%
3.1V
1.3%
50 ft 1.9V
0.8%
2.5V
1.0%
3.7V
1.6%
5.0V
2.1%
6.2V
2.6%
75 ft 2.8V
1.2%
3.7V
1.6%
5.6V
2.3%
7.4V
3.1%
9.3V
3.9%
100 ft 3.7V
1.6%
5.0V
2.1%
7.4V
3.1%
9.9V
4.1%
12.4V
5.2%
125 ft 4.7V
1.9%
6.2V
2.6%
9.3V
3.9%
12.4V
5.2%
15.5V
6.5%
150 ft 5.6V
2.3%
7.4V
3.1%
11.2V
4.7%
14.9V
6.2%
18.6V
7.8%
200 ft 7.4V
3.1%
9.9V
4.1%
14.9V
6.2%
19.8V
8.3%
24.8V
10.3%
250 ft 9.3V
3.9%
12.4V
5.2%
18.6V
7.8%
24.8V
10.3%
31.0V
12.9%
300 ft 11.2V
4.7%
14.9V
6.2%
22.3V
9.3%
29.8V
12.4%
37.2V
15.5%
400 ft 14.9V
6.2%
19.8V
8.3%
29.8V
12.4%
39.7V
16.5%
49.6V
20.7%
500 ft 18.6V
7.8%
24.8V
10.3%
37.2V
15.5%
49.6V
20.7%
62.0V
25.8%

How Far Can You Run 10 AWG?

One of the most common questions electricians and homeowners ask is how far a particular wire gauge can run before exceeding the NEC voltage drop recommendation. The answer depends on the circuit voltage, the current draw, and whether you are using the 3% branch circuit limit or the 5% feeder-plus-branch limit. Below are maximum one-way distances for 10 AWG copper at 3% voltage drop:

Load 120V Max Distance 240V Max Distance
15 Amps 96 ft 193 ft
20 Amps 72 ft 145 ft
30 Amps 48 ft 96 ft

These distances represent the maximum one-way run from the breaker panel to the load. If your run exceeds these limits, you must use a larger wire gauge to keep the voltage drop within acceptable limits. For feeder circuits where the 5% combined limit applies, you can extend the run by approximately 67% beyond the 3% distances shown above, but only if the branch circuit portion stays within its own 3% allowance.

Common Uses for 10 AWG

10 AWG is used for 30-amp branch circuits and is commonly found in dryer circuits, window air conditioner circuits, and small appliance circuits requiring higher amperage. It is also the standard wire size for 30-amp RV outlets (TT-30) and many well pump circuits. At 240 volts, a 10 AWG circuit can deliver up to 7,200 watts, making it suitable for electric water heaters and small workshop equipment.

When selecting 10 AWG for your installation, always verify that the ampacity meets or exceeds the circuit breaker rating, the voltage drop is within NEC recommendations for the run distance, and the terminations at both ends are rated for the conductor material and size. For circuits serving continuous loads (operating 3 hours or more), the conductor must be sized at 125% of the continuous load current. Consult NEC Article 210 for branch circuit requirements and Article 215 for feeder circuit requirements.

Other Wire Sizes

Browse specifications and voltage drop tables for other wire gauges. Selecting the correct wire size requires balancing ampacity, voltage drop, cost, and installation practicality.