100A Motor Circuit — Wire Size Guide

100-amp, three-phase, 480-volt motor circuit for large industrial motors rated at 50-75 horsepower. Industrial facilities use 480-volt power to reduce conductor size and voltage drop over long runs. These circuits require properly rated motor starters, overload relays, and disconnect switches. Wire sizing follows NEC 430.22 using Table 430.250 full-load current values.

Voltage
480V
Amperage
100A
Phase
Three-Phase
NEC Reference
NEC 430.22, 430.52, Table 430.250

Copper Wire Size by Distance

The table below shows the recommended copper wire gauge for a 100A Motor Circuit circuit (480V, 100A, Three-Phase) at various one-way distances from the panel. Two voltage drop limits are shown: 3% for branch circuits and 5% for feeder-plus-branch combined. The ampacity column is based on NEC Table 310.16 at 75 degrees C. When the 3% and 5% columns show different gauges, the distance is long enough that voltage drop — not ampacity — is the controlling factor, and you must use the gauge appropriate for your circuit type.

Distance 3% Drop Gauge 3% Drop (V) 3% Drop (%) 5% Drop Gauge 5% Drop (V) 5% Drop (%)
25 ft 3 AWG 1.06 0.22% 3 AWG 1.06 0.22%
50 ft 3 AWG 2.12 0.44% 3 AWG 2.12 0.44%
75 ft 3 AWG 3.18 0.66% 3 AWG 3.18 0.66%
100 ft 3 AWG 4.24 0.88% 3 AWG 4.24 0.88%
125 ft 3 AWG 5.30 1.11% 3 AWG 5.30 1.11%
150 ft 3 AWG 6.37 1.33% 3 AWG 6.37 1.33%
200 ft 3 AWG 8.49 1.77% 3 AWG 8.49 1.77%
250 ft 3 AWG 10.61 2.21% 3 AWG 10.61 2.21%
300 ft 3 AWG 12.73 2.65% 3 AWG 12.73 2.65%
400 ft 2 AWG 13.44 2.80% 3 AWG 16.97 3.54%
500 ft 1 AWG 13.34 2.78% 3 AWG 21.22 4.42%

Aluminum Wire Size by Distance

Aluminum conductors cost less and weigh less than copper but have higher resistance, requiring larger gauge sizes to carry the same current. The table below shows the recommended aluminum wire gauge for this 100A Motor Circuit circuit at various distances. Aluminum is a practical choice for longer feeder runs and service entrance conductors where the material savings justify the larger conductor size. All aluminum terminations must be rated for aluminum use (AL-CU marking) and treated with anti-oxidant compound.

Distance 3% Drop Gauge 3% Drop (V) 3% Drop (%) 5% Drop Gauge 5% Drop (V) 5% Drop (%)
25 ft 1 AWG 1.10 0.23% 1 AWG 1.10 0.23%
50 ft 1 AWG 2.19 0.46% 1 AWG 2.19 0.46%
75 ft 1 AWG 3.29 0.68% 1 AWG 3.29 0.68%
100 ft 1 AWG 4.38 0.91% 1 AWG 4.38 0.91%
125 ft 1 AWG 5.48 1.14% 1 AWG 5.48 1.14%
150 ft 1 AWG 6.57 1.37% 1 AWG 6.57 1.37%
200 ft 1 AWG 8.76 1.83% 1 AWG 8.76 1.83%
250 ft 1 AWG 10.95 2.28% 1 AWG 10.95 2.28%
300 ft 1 AWG 13.15 2.74% 1 AWG 13.15 2.74%
400 ft 1/0 AWG 13.93 2.90% 1 AWG 17.53 3.65%
500 ft 2/0 AWG 13.77 2.87% 1 AWG 21.91 4.56%

Installation Tips for 100A Motor Circuit

Proper installation is just as important as selecting the correct wire size. The following tips address the key NEC requirements and best practices specific to 100a motor circuit circuits. Always verify these requirements against the current edition of the NEC and your local code amendments before beginning work.

  • Motor circuits must be sized based on the full-load current from NEC Table 430.248 (single-phase) or Table 430.250 (three-phase), not the motor nameplate current.
  • The branch-circuit overcurrent protection device must be sized per NEC Table 430.52. Motor overload protection is sized separately at 115-125% of the nameplate full-load current.
  • All wire connections must be made with listed connectors and torqued to manufacturer specifications. Use anti-oxidant compound on all aluminum connections.
  • Verify local code amendments, as your jurisdiction may have requirements beyond the NEC minimum. Always pull a permit and schedule inspections for electrical work.

NEC Code References

The 100A Motor Circuit circuit is governed by NEC 430.22, 430.52, Table 430.250. These NEC sections specify the minimum requirements for circuit sizing, overcurrent protection, grounding, and installation methods. The wire sizing in this guide is based on the following NEC tables and articles:

  • NEC Table 310.16 — Ampacity of insulated conductors rated 0-2000V in raceways, cables, or direct buried. Provides the maximum current each gauge can safely carry at 60, 75, and 90 degrees C.
  • NEC Chapter 9, Table 8 — Conductor properties including DC resistance per 1000 feet for uncoated copper and aluminum. These resistance values are used in the voltage drop formula.
  • NEC 210.19(A) Informational Note No. 4 — Recommends that branch circuit conductors be sized so that the voltage drop does not exceed 3%, and the combined feeder plus branch circuit drop does not exceed 5%.
  • NEC 215.2(A)(1) Informational Note No. 2 — Same voltage drop recommendation applied to feeder conductors.
  • NEC 430.22, 430.52, Table 430.250 — Specific requirements for this application, including circuit sizing, overcurrent protection, and installation methods.

Other Applications

Browse wire sizing guides for other common electrical circuits. Each page includes pre-computed wire sizes at multiple distances, installation tips, and NEC code references.